Appendix D—Modbus Register MapPower Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 327717 Q3 Function Select UINT16 RW NVDefault: 56EnumConfig CRCRun LockAdmin LockUSB LockBackup MemOutput Function Select for General Purpose Output 3. Available when thisoutput is not used by the Operation Mode. Default = none, If used by theApplication Mode = Reserved. (For non-latching relay, 0 = de-energizedand 1 = energized. For latching relay, 0 = no change and 1 = set). A softreset is required after modifying this parameter, continued.Table 128. C445 Modbus Register Map, continuedRegister Name Attribute DescriptionValue Description40 Warning Status Bits - Voltage unbalance41 Warning Status Bits - Voltage phase loss42 Warning Status Bits - Power factor deviation43 Warning Status Bits - Jam44 Warning Status Bits - Instantaneous over current45 Warning Status Bits - Current unbalance46 Warning Status Bits - Current phase loss47 Warning Status Bits - Ground current48 Warning Status Bits - Reserved49 Warning Status Bits - Over voltage50 Warning Status Bits - Under voltage51 Tripped Status Bits - Under voltage52 Tripped Status Bits - Over voltage53 Tripped Status Bits - Reserved54 Base Control Module Field Output control word - Bit 055 Base Control Module Field Output control word - Bit 156 Base Control Module Field Output control word - Bit 257 Base Control Module Field Output control word - Bit 358 Shunt trip output bit - Shunt trip output bit59 Warning Reason - HRGF pulse detection60 Warning Reason - Peak demand61 Digital Input Status - Base Control Module Input I462 Digital Input Status - Base Control Module Input I363 Digital Input Status - Base Control Module Input I264 Digital Input Status - Base Control Module Input I165 Fail Safe - Ground current fault65535 Reserved