Appendix C—Optional Communication CardsPower Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 24712 2 Current Average MOTOR_I_AVE_SCALED:Average Motor Current Scaled.Scaled by parameter “I Scale Factor.”14 2 Voltage L1-L2 LINE_V_LL_AB_RMS:Phase A RMS Voltage L1-L2 (V)16 2 Voltage L2-L3 LINE_V_LL_BC_RMS:Phase B RMS Voltage L2-L3 (V)18 2 Voltage L3-L1 LINE_V_LL_CA_RMS:Phase C RMS Voltage L3-L1 (V)20 2 Voltage Average LINE_V_LN_AVE_RMS:Average RMS Voltage (V)22 2 Digital Inputs Bits 0-7 = Inputs for the first digital input cardBits 8-15 = Inputs for the second digital input card24 2 Digital Inputs Bits 0-7 = Inputs for the third digital input cardBits 8-15 = Inputs for the fourth digital input card26 2 Digital Inputs Bits 0-7 = Inputs for the fifth digital input cardBits 8-15 = Inputs for the sixth digital input card28 20 Analog Inputs 10 Input words of data for analog inputs and status word(s)Input Instance 114 (0x72): Status, Current, Voltage, Trip with Extended Analog and Digital Inputs 2Length = 68 BytesByteOffsetSize(bytes) Name Description0 2 Device Status C445_DEVICE_STATUSBit 0: Faulted/TrippedBit 1: WarningBit 2: Output #1Bit 3: Output #2Bit 4: Input #1Bit 5: Input #2Bit 6: Input #3Bit 7: Input #4Bit 8: Running1Bit 9: Running2Bit 10: Remote or CtrlFromNetBit 11: Output #3Bit 12: ReservedBit 13: InhibitedBit 14: ReadyBit 15: AtRef or Up-To-Speed2 2 Current L1 MOTOR_I_A_SCALED:Phase A (L1) Motor Current Scaled.Scaled by parameter “I Scale Factor.”4 2 Current L2 MOTOR_I_B_SCALED:Phase B (L2) Motor Current Scaled.Scaled by parameter “I Scale Factor.”Input Instance 113 (0x71): Status, Current, Voltage, Trip with Extended Analog and Digital Inputs, continuedLength = 48 BytesByteOffsetSize(bytes) Name Description