Appendix D—Modbus Register MapPower Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 3992559 Fault/Warning configuration BYTE RW NVArray size: 4Default: 0BitfieldConfig CRCAdmin LockUSB LockBackup MemFault/Warning configuration - When a bit is set to 0, a fault is thrown,when set to 1, a warning is thrown.2561 Logic error info - Program Id UINT16 RODefault: 0Logic error info - Program IdLogic error info - Program Id2562 Logic error info - ProgramCounterUINT32 RODefault: 0Logic error info - Program CounterLogic error info - Program Counter2564 Logic error info - Error Data UINT32 RODefault: 0Logic error info - Error DataLogic error info - Error Data2566 Logic Run Control BYTE RW NVDefault: 0BitfieldConfig CRCAdmin LockUSB LockBackup MemLogic Run Control2567 Logic Run Status BYTE RODefault: 0BitfieldLogic Run Status2568 ELC IO Speciality Moduleconfig locationUINT8 RW NVDefault: 0EnumAdmin LockBackup MemELC IO Speciality Module config locationTable 128. C445 Modbus Register Map, continuedRegister Name Attribute DescriptionBit Description Coil0 Logic program underrun 409291 Logic program overrun 409302 Logic task watchdog 409313 Logic instruction invalid instance number 409324 Logic instruction invalid argument 409335 Logic math - divide by zero 409346 Logic math - underflow 409357 Logic math - overflow 409368 ELC IO Comm loss 409379 ELC IO Comm error 4093810 Generic Modbus slave comm loss 4093911 Generic Modbus slave comm error 4094012 Logic Program accessing ELC IO but ELC IO notconfigured40941Bit Description Coil0 Run 41041Bit Description Coil0 Logic Running 41057Bit Description Coil0 C445 ELC10