Appendix C—Optional Communication CardsPower Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 249Input Instance 116 (0x74): Full MonitoringLength = 41 BytesByteOffsetSize(bytes) Name Description0 2 Device Status PACKED_C445_DEVICE_STATUS:Device Bit ArrayBit 0: Faulted/TrippedBit 1: WarningBit 2: Output #1Bit 3: Output #2Bit 4: Input #1Bit 5: Input #2Bit 6: Input #3Bit 7: Input #4Bit 8: Running1Bit 9: Running2Bit 10: Remote or CtrlFromNetBit 11: Output #3Bit 12: ReservedBit 13: InhibitedBit 14: ReadyBit 15: AtRef or Up-To-Speed2 2 Current I1 MOTOR_I_A_SCALED:Phase A (L1) Motor Current Scaled.Scaled by parameter “I Scale Factor.”4 2 Current I2 MOTOR_I_B_SCALED:Phase B (L2) Motor Current Scaled.Scaled by parameter “I Scale Factor.”6 2 Current I3 MOTOR_I_C_SCALED:Phase C (L3) Motor Current Scaled.Scaled by parameter “I Scale Factor.”8 2 Field inputs LOGIC_INPUT_STATE_BITFIELD:Digital Input Status.10 2 Current Average MOTOR_I_AVE_SCALED:Average Motor Current Scaled.Scaled by parameter “I Scale Factor.”12 2 VoltageL1-L2LINE_V_LL_AB_RMS:Phase A RMS Voltage L1-L2 (V)14 2 VoltageL2-L3LINE_V_LL_BC_RMS:Phase B RMS Voltage L2-L3 (V)16 2 VoltageL3-L1LINE_V_LL_CA_RMS:Phase C RMS Voltage L3-L1 (V)18 2 VoltageAverageLINE_V_LN_AVE_RMS:Average RMS Voltage (V)20 4 Motor Power POWER_WATTS:Motor PowerWatts24 1 Voltage UnbalancePercentageLINE_V_UNBALANCE_PERC:Max Deviation from Average VoltageDivided by Average Voltage (%).25 1 Current UnbalancePercentageMOTOR_I_UNBALANCE_PERC:Max Deviation from Average CurrentDivided by Average Current (%)