18.3.5.3 SignalsTable 728:MVGAPC Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionIN REAL 0 Analog input valueTable 729:MVGAPC Output signalsName Type DescriptionVALUE REAL Magnitude of deadband valueRANGE INTEGER Range18.3.5.4 SettingsTable 730:MVGAPC Non group settings (basic)Name Values (Range) Unit Step Default DescriptionBasePrefix micromilliunitkiloMegaGigaTera- - unit Base prefix (multiplication factor)MV db 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sMV zeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of rangeMV hhLim -5000.00 - 5000.00 xBase 0.01 900.00 High High limit multiplied with the baseprefix (multiplication factor)MV hLim -5000.00 - 5000.00 xBase 0.01 800.00 High limit multiplied with the base prefix(multiplication factor)MV lLim -5000.00 - 5000.00 xBase 0.01 -800.00 Low limit multiplied with the base prefix(multiplication factor)MV llLim -5000.00 - 5000.00 xBase 0.01 -900.00 Low Low limit multiplied with the baseprefix (multiplication factor)MV min -5000.00 - 5000.00 xBase 0.01 -1000.00 Minimum value multiplied with the baseprefix (multiplication factor)MV max -5000.00 - 5000.00 xBase 0.01 1000.00 Maximum value multiplied with the baseprefix (multiplication factor)MV dbType CyclicDead bandInt deadband- - Dead band Reporting typeMV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)Section 18 1MRK502052-UEN BStation communication998Technical manual