PulseTimeOndelayOUTPUT 1PulseTimeOndelayOUTPUT 2PulseTimeOndelayOUTPUT 3INPUT 17INPUT 32INPUT 1INPUT 16IEC09000612-3-en.vsd³1³1³1³1&&&&&&³1³1tttOffdelayttttOffdelaytOffdelaytModeOutput1=PulsedModeOutput2=PulsedModeOutput3=PulsedIEC09000612 V3 ENFigure 374: Trip matrix internal logicOutput signals from TMAGAPC are typically connected to other logic blocks ordirectly to output contacts in the IED. When used for direct tripping of the circuitbreaker(s) the pulse time shall be set to at least 0.150 seconds in order to obtainsatisfactory minimum duration of the trip pulse to the circuit breaker trip coils.15.2.7 Technical dataTable 495:Number of TMAGAPC instancesFunction Quantity with cycle time3 ms 8 ms 100 msTMAGAPC 6 6 -15.3 Logic for group alarm ALMCALH15.3.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLogic for group alarm ALMCALH - -Section 15 1MRK502052-UEN BLogic802Technical manual