Name Values (Range) Unit Step Default DescriptiontMin 1.0 - 120.0 s 0.1 10.0 Minimum time, used in operatecharacteristictMax 100.0 - 2000.0 s 0.1 300.0 Maximum time, used in operatecharacteristictCutOff 10.0 - 2000.0 s 0.1 120.0 Cut-off time, used in operatecharacteristictReset 10.0 - 2000.0 s 0.1 120.0 Time required for Theta to reset from100% to 0%Table 251:GSPTTR Group settings (advanced)Name Values (Range) Unit Step Default DescriptionPosSeqFactor 0.0 - 10.0 - 0.1 1.0 Weighting factor for the positive sequencecurrentNegSeqFactor 0.0 - 10.0 - 0.1 6.0 Weighting factor for the negativesequence currentTable 252:GSPTTR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionMeasurCurrent RMSPosSeqNegSeq- - RMS Measured current quantity (RMS orweighted sum of positive and negativesequence)GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Valuegroups8.15.6 Monitored dataTable 253:GSPTTR Monitored dataName Type Values (Range) Unit DescriptionIMEAS REAL - A Measured current, usedfor calculation of operatetimeTHETA REAL - % Overload in percent of settrip level (i.e. Trip=100%)8.15.7 Operation principleThe stator overload protection can be illustrated in three separate sub-blocks, seeFigure213.1MRK502052-UEN B Section 8Current protection455Technical manual