15.7.2.1 Function blockINDCOMBSPQTSP_IN*TIME*BLOCKED*SUBST*INVALID*TEST*SP_OUTIEC15000146.vsdIEC15000146 V1 ENFigure 388: INDCOMBSPQT function block15.7.2.2 SignalsTable 549:INDCOMBSPQT Input signalsName Type Default DescriptionSP_IN BOOLEAN 0 Single point indicationTIME GROUPSIGNAL0 TimestampBLOCKED BOOLEAN 0 Blocked for updateSUBST BOOLEAN 0 SubstituedINVALID BOOLEAN 0 Invalid valueTEST BOOLEAN 0 TestmodeTable 550:INDCOMBSPQT Output signalsName Type DescriptionSP_OUT BOOLEAN Single point indication15.7.2.3 Technical dataTable 551:Number of INDCOMBSPQT instancesLogic block Quantity with cycle time3 ms 8 ms 100 msINDCOMBSPQT - 10 1015.7.3 Single point input signal attributes converting function blockINDEXTSPQTThe value part of the single point input signal SI_IN is copied to SI_OUT output. Thetime part of single point input is copied to the TIME output. The state bits in thecommon part and the indication part of the input signal are copied to the correspondingstate output.1MRK502052-UEN B Section 15Logic823Technical manual