13.3.5 SettingsTable 357:VDSPVC Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Mode Off / OnUd>MainBlock 10.0 - 80.0 %UB 0.1 20.0 Blocking picked up voltage level in % ofUBase when main fuse failsUd>PilotAlarm 10.0 - 80.0 %UB 0.1 30.0 Alarm picked up voltage level in % ofUBase when pilot fuse failsSealIn OffOn- - On Seal in functionality Off/OnUSealIn 0.0 - 100.0 %UB 0.1 70.0 Operate level of seal-in voltage in % ofUBaseTable 358:VDSPVC Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base ValuegroupsTable 359:VDSPVC Non group settings (advanced)Name Values (Range) Unit Step Default DescriptionConTypeMain Ph-NPh-Ph- - Ph-N Selection of connection type for main fusegroupConTypePilot Ph-NPh-Ph- - Ph-N Selection of connection type for pilot fusegroup13.3.6 Monitored dataTable 360:VDSPVC Monitored dataName Type Values (Range) Unit DescriptionUL1DIF_A REAL - kV Differential voltage phaseL1 for alarm functionalityUL2DIF_A REAL - kV Differential voltage phaseL2 for alarm functionalityUL3DIF_A REAL - kV Differential voltage phaseL3 for alarm functionalityUL1DIF_B REAL - kV Differential voltage phaseL1 for block functionalityUL2DIF_B REAL - kV Differential voltage phaseL2 for block functionalityUL3DIF_B REAL - kV Differential voltage phaseL3 for block functionality1MRK502052-UEN B Section 13Secondary system supervision621Technical manual