21.2.10.4 SettingsTable 908:IOMIN Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - On Binary input/output module in operation(On) or not (Off)DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputsOscBlock 1 - 40 Hz 1 40 Oscillation block limitOscRelease 1 - 30 Hz 1 30 Oscillation release limit21.2.10.5 Monitored dataTable 909:IOMIN Monitored dataName Type Values (Range) Unit DescriptionSTATUS BOOLEAN 0=Ok1=Error- Binary input part of IOMmodule statusTable 910:IOMOUT Monitored dataName Type Values (Range) Unit DescriptionBO1VALUE BOOLEAN 1=10=0- Binary output 1 valueBO1FORCE BOOLEAN 0=Normal1=Forced- Binary output 1 forceBO1 BOOLEAN 0=Normal1=Forced2=Blocked- Binary output 1 statusBO2VALUE BOOLEAN 1=10=0- Binary output 2 valueBO2FORCE BOOLEAN 0=Normal1=Forced- Binary output 2 forceBO2 BOOLEAN 0=Normal1=Forced2=Blocked- Binary output 2 statusBO3VALUE BOOLEAN 1=10=0- Binary output 3 valueBO3FORCE BOOLEAN 0=Normal1=Forced- Binary output 3 forceBO3 BOOLEAN 0=Normal1=Forced2=Blocked- Binary output 3 statusBO4VALUE BOOLEAN 1=10=0- Binary output 4 valueBO4FORCE BOOLEAN 0=Normal1=Forced- Binary output 4 forceBO4 BOOLEAN 0=Normal1=Forced2=Blocked- Binary output 4 statusTable continues on next page1MRK502052-UEN B Section 21IED hardware1177Technical manual