setting the Report Intermediate Position = Off. See the settings for RS485 and opticalserial communication for more information.Input SELECT is a single-indication signal, and it is also GI enabled. State transitionsto ON and OFF are reported spontaneously.When input BLOCK is ON, the function will ignore GI requests and cease allmonitoring activity. Consequently, no transitions will be detected.The I103POSCMD function is also equipped with two additional commands: Operateand Cancel. These are hidden in ACT and respond only to base INF +2 and +3respectively. The base INF (Information Number) parameter is an IEC 60870-5-103identifier that associates a function in a 103 Master (such as Scada) with its equivalentin the IED.18.6.14.2 IdentificationFunction description Function blocknameIEC 60617identificationANSI/IEEE C37.2device numberIED commands with position and selectfor IEC 60870-5-103I103POSCMD - -18.6.14.3 Function blockIEC10000286-1-en.vsdI103POSCMDBLOCKPOSITIONSELECTIEC10000286 V1 ENFigure 483: I103POSCMD function block18.6.14.4 SignalsTable 775:I103POSCMD Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of commandPOSITION INTEGER 0 Position of controllable objectSELECT BOOLEAN 0 Select of controllable object18.6.14.5 SettingsTable 776:I103POSCMD Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function typeInfNo 160 - 236 - 4 160 Information number for command output1MRK502052-UEN B Section 18Station communication1049Technical manual