14.10.5 SettingsTable 486:SINGLECMD Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffSteadyPulsed- - Off Operation Off / On14.10.6 Operation principleSingle command, 16 signals (SINGLECMD) function has 16 binary output signals.The outputs can be individually controlled from a substation automation system orfrom the local HMI. Each output signal can be given a name with a maximum of 13characters in PCM600.The output signals can be of the types Off, Steady, or Pulse. This configuration settingis done via the local HMI or PCM600 and is common for the whole function block.The length of the output pulses are 100 ms. In steady mode, SINGLECMD functionhas a memory to remember the output values at power interruption of the IED. Alsoa BLOCK input is available used to block the updating of the outputs.The output signals, OUT1 to OUT16, are available for configuration to built-infunctions or via the configuration logic circuits to the binary outputs of the IED.Section 14 1MRK502052-UEN BControl790Technical manual