18.10.3 Function blockIEC10000250-1-en.vsdGOOSEINTRCVBLOCK ^INTOUTDATAVALIDCOMMVALIDTESTIEC10000250 V1 ENFigure 487: GOOSEINTRCV function block18.10.4 SignalsTable 797:GOOSEINTRCV Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionTable 798:GOOSEINTRCV Output signalsName Type DescriptionINTOUT INTEGER Integer outputDATAVALID BOOLEAN Data valid for integer outputCOMMVALID BOOLEAN Communication valid for integer outputTEST BOOLEAN Test output18.10.5 SettingsTable 799:GOOSEINTRCV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/On18.10.6 Operation principleThe DATAVALID output will be HIGH if the incoming message is with valid data.The COMMVALID output will become LOW when the sending IED is under totalfailure condition and the GOOSE transmission from the sending IED does not happen.The TEST output will go HIGH if the sending IED is in test mode.The input of this GOOSE block must be linked in SMT by means ofa cross to receive the integer values.1MRK502052-UEN B Section 18Station communication1069Technical manual