Name Type DescriptionSTRVL3 BOOLEAN Fault detected in phase L3 - reverse directionSTRVPE BOOLEAN Fault with earth connection detected - reversedirectionSTFW1PH BOOLEAN Single-phase fault detected - forward directionSTFW2PH BOOLEAN Two-phase fault detected - forward directionSTFW3PH BOOLEAN Three-phase fault detected - forward directionSTPE BOOLEAN Ph-E zone measurement enabled - any directionSTPP BOOLEAN Ph-Ph zone measurement enabled - any direction7.4.5 SettingsTable 94:ZMFCPDIS Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Mode Off / OnOperationSC NoSeriesCompSeriesComp- - NoSeriesComp Selection of series compensationoperation Off / OnRLdFw 0.01 - 5000.00 Ohm/p 0.01 60.00 Resistance determining the loadimpedance area - forwardRLdRv 0.01 - 5000.00 Ohm/p 0.01 60.00 Resistance determining the loadimpedance area - reverseXLd 0.01 - 10000.00 Ohm/p 0.01 400.00 Reactance determining the loadimpedance areaArgLd 5 - 70 Deg 1 30 Angle determining the load impedanceareaCVTtype AnyPassive typeNone (Magnetic)- - Passive type CVT selection determining the filtering ofthe functionOpModeZ1 Disable-ZoneEnable Ph-EEnable PhPhEnable Ph-E PhPh- - Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E loops,zone 1X1FwPPZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive seq. reactance reach, Ph-Ph,zone 1, forward dir.R1FwPPZ1 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistive reach, Ph-Ph, zone1, forward dir.RFPPZ1 0.01 - 9000.00 Ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, zone 1,forw & rev dir.X1RvPPZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Pos. seq. react. reach, Ph-Ph, zone 1,reverse directionX1FwPEZ1 0.01 - 3000.00 Ohm/p 0.01 30.00 Positive seq. reactance reach, Ph-E, zone1, forward dir.R1FwPEZ1 0.00 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistive reach, Ph-E, zone1, forward dir.X0FwPEZ1 0.01 - 9000.00 Ohm/p 0.01 100.00 Zero seq. reactance reach, Ph-E, zone 1,forward directionTable continues on next page1MRK502052-UEN B Section 7Impedance protection231Technical manual