Name Type DescriptionSFREQ REAL Slip frequencySLIPZOHM REAL Slip impedance in ohmsSLIPZPER REAL Slip impedance in percent of ZBaseUCOS REAL UCosPhi voltageUCOSPER REAL UCosPhi voltage in percent of UBase7.5.5 SettingsTable 101:PSPPPAM Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation On / OffOperationZ1 OffOn- - On Operation Zone1 On / OffOperationZ2 OffOn- - On Operation Zone2 On / OffImpedanceZA 0.00 - 1000.00 % 0.01 10.00 Forward impedance in % of ZbaseImpedanceZB 0.00 - 1000.00 % 0.01 10.00 Reverse impedance in % of ZbaseImpedanceZC 0.00 - 1000.00 % 0.01 10.00 Impedance of zone1 limit in % of ZbaseAnglePhi 72.00 - 90.00 Deg 0.01 85.00 Angle of the slip impedance lineStartAngle 0.0 - 180.0 Deg 0.1 110.0 Rotor angle for the start signalTripAngle 0.0 - 180.0 Deg 0.1 90.0 Rotor angle for the trip1 and trip2 signalsN1Limit 1 - 20 - 1 1 Count limit for the trip1 signalN2Limit 1 - 20 - 1 3 Count limit for the trip2 signalTable 102:PSPPPAM Group settings (advanced)Name Values (Range) Unit Step Default DescriptionResetTime 0.000 - 60.000 s 0.001 5.000 Time without slip to reset all signalsTable 103:PSPPPAM Non group settings (basic)Name Values (Range) Unit Step Default DescriptionMeasureMode PosSeqL1L2L2L3L3L1- - PosSeq Measuring mode (PosSeq, L1L2, L2L3,L3L1)InvertCTcurr NoYes- - No Invert current directionGlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base ValuegroupsSection 7 1MRK502052-UEN BImpedance protection254Technical manual