Name Values (Range) Unit Step Default DescriptionValueMinCh4 -10000000000.000- 10000000000.000- 0.001 4.000 Min primary value corr. to IMinCh4ValueMaxCh4 -10000000000.000- 10000000000.000- 0.001 20.000 Max primary value corr. to IMaxCh4EnDeadBandCh5 OffOn- - Off Enable amplitude deadband reporting forchannel 5DeadBandCh5 0.00 - 20.00 mA 0.01 1.00 Deadband amplitude for channel 5IMinCh5 -25.00 - 25.00 mA 0.01 4.00 Min current of transducer for Channel 5IMaxCh5 -25.00 - 25.00 mA 0.01 20.00 Max current of transducer for Channel 5ValueMinCh5 -10000000000.000- 10000000000.000- 0.001 4.000 Min primary value corr. to IMinCh5ValueMaxCh5 -10000000000.000- 10000000000.000- 0.001 20.000 Max primary value corr. to IMaxCh5EnDeadBandCh6 OffOn- - Off Enable amplitude deadband reporting forchannel 6DeadBandCh6 0.00 - 20.00 mA 0.01 1.00 Deadband amplitude for channel 6IMinCh6 -25.00 - 25.00 mA 0.01 4.00 Min current of transducer for Channel 6IMaxCh6 -25.00 - 25.00 mA 0.01 20.00 Max current of transducer for Channel 6ValueMinCh6 -10000000000.000- 10000000000.000- 0.001 4.000 Min primary value corr. to IMinCh6ValueMaxCh6 -10000000000.000- 10000000000.000- 0.001 20.000 Max primary value corr. to IMaxCh621.2.11.5 Monitored dataTable 916:MIM Monitored dataName Type Values (Range) Unit DescriptionSTATUS BOOLEAN 0=Ok1=Error- Milliampere input modulestatusCH1 REAL - - Analog input 1CH2 REAL - - Analog input 2CH3 REAL - - Analog input 3CH4 REAL - - Analog input 4CH5 REAL - - Analog input 5CH6 REAL - - Analog input 6CH1 REAL - A Service value analoginput 1CH2 REAL - A Service value analoginput 2CH3 REAL - A Service value analoginput 3Table continues on next pageSection 21 1MRK502052-UEN BIED hardware1184Technical manual