The sum of the value on each INx corresponds to the integer presented on the outputOUT on the function block B16IName of input Type Default Description Value whenactivatedValue whendeactivatedIN1 BOOLEAN 0 Input 1 1 0IN2 BOOLEAN 0 Input 2 2 0IN3 BOOLEAN 0 Input 3 4 0IN4 BOOLEAN 0 Input 4 8 0IN5 BOOLEAN 0 Input 5 16 0IN6 BOOLEAN 0 Input 6 32 0IN7 BOOLEAN 0 Input 7 64 0IN8 BOOLEAN 0 Input 8 128 0IN9 BOOLEAN 0 Input 9 256 0IN10 BOOLEAN 0 Input 10 512 0IN11 BOOLEAN 0 Input 11 1024 0IN12 BOOLEAN 0 Input 12 2048 0IN13 BOOLEAN 0 Input 13 4096 0IN14 BOOLEAN 0 Input 14 8192 0IN15 BOOLEAN 0 Input 15 16384 0IN16 BOOLEAN 0 Input 16 32768 0The sum of the numbers in column “Value when activated” when all INx (where1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can beconverted to an integer by the B16I function block.15.10.7 Technical dataTable 591:Number of B16I instancesFunction Quantity with cycle time3 ms 8 ms 100 msB16I 6 4 815.11 Boolean 16 to Integer conversion with logic noderepresentation BTIGAPC15.11.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberBoolean 16 to integer conversion withlogic node representationBTIGAPC - -1MRK502052-UEN B Section 15Logic839Technical manual