18.6.11.2 IdentificationFunction description Function blocknameIEC 60617identificationANSI/IEEE C37.2device numberIED commands for IEC 60870-5-103 I103IEDCMD - -18.6.11.3 Function blockIEC10000283-1-en.vsdI103IEDCMDBLOCK 19-LEDRS23-GRP124-GRP225-GRP326-GRP4IEC10000283 V1 ENFigure 480: I103IEDCMD function block18.6.11.4 SignalsTable 766:I103IEDCMD Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of commandsTable 767:I103IEDCMD Output signalsName Type Description19-LEDRS BOOLEAN Information number 19, reset LEDs23-GRP1 BOOLEAN Information number 23, activate setting group 124-GRP2 BOOLEAN Information number 24, activate setting group 225-GRP3 BOOLEAN Information number 25, activate setting group 326-GRP4 BOOLEAN Information number 26, activate setting group 418.6.11.5 SettingsTable 768:I103IEDCMD Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 255 Function type (1-255)1MRK502052-UEN B Section 18Station communication1045Technical manual