Name Values (Range) Unit Step Default DescriptiontReset4 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 4tPCrv4 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 4tACrv4 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmablecurve for step 4tBCrv4 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmablecurve for step 4tCCrv4 0.1 - 10.0 - 0.1 1.0 Parameter C for customer programmablecurve for step 4tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customerprogrammable curve for step 4tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customerprogrammable curve for step 4tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customerprogrammable curve for step 4HarmBlock4 OffOn- - Off Enable block of step 4 from harmonicrestrainTable 162:OC4PTOC Non group settings (basic)Name Values (Range) Unit Step Default DescriptionMeasType DFTRMS- - DFT Selection between DFT and RMSmeasurementGlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Valuegroups8.2.6 Monitored dataTable 163:OC4PTOC Monitored dataName Type Values (Range) Unit DescriptionDIRL1 INTEGER 1=Forward2=Reverse0=No direction- Direction for phase1DIRL2 INTEGER 1=Forward2=Reverse0=No direction- Direction for phase2DIRL3 INTEGER 1=Forward2=Reverse0=No direction- Direction for phase3IL1 REAL - A Current in phase L1IL2 REAL - A Current in phase L2IL3 REAL - A Current in phase L3Section 8 1MRK502052-UEN BCurrent protection344Technical manual