Name Type Default DescriptionINPUT9 BOOLEAN 0 Binary input 9INPUT10 BOOLEAN 0 Binary input 10INPUT11 BOOLEAN 0 Binary input 11INPUT12 BOOLEAN 0 Binary input 12INPUT13 BOOLEAN 0 Binary input 13INPUT14 BOOLEAN 0 Binary input 14INPUT15 BOOLEAN 0 Binary input 15INPUT16 BOOLEAN 0 Binary input 16Table 501:WRNCALH Output signalsName Type DescriptionWARNING BOOLEAN OR function betweeen inputs 1 to 1615.4.5 SettingsTable 502:WRNCALH Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / On15.4.6 Operation principleThe logic for group warning WRNCALH block is provided with 16 input signals and1 WARNING output signal. The function block incorporates internal logic OR gate inorder to provide grouping of connected input signals to the output WARNING signalfrom the function block.When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, theWARNING output signal will get logical value 1.The function has a drop-off delay of 200 ms when all inputs are reset to provide asteady signal.WARNING³1200 mstIEC13000192-1-en.vsdINPUT1INPUT16IEC13000192 V1 ENSection 15 1MRK502052-UEN BLogic806Technical manual