Name Type DescriptionHMICTR7 INTEGER Bitmask output 7 to local remote LHMI inputHMICTR8 INTEGER Bitmask output 8 to local remote LHMI inputHMICTR9 INTEGER Bitmask output 9 to local remote LHMI inputHMICTR10 INTEGER Bitmask output 10 to local remote LHMI inputHMICTR11 INTEGER Bitmask output 11 to local remote LHMI inputHMICTR12 INTEGER Bitmask output 12 to local remote LHMI input14.3.5.3 SettingsTable 407:LOCREM Non group settings (basic)Name Values (Range) Unit Step Default DescriptionControlMode Internal LR-switchExternal LR-switch- - Internal LR-switch Control mode for internal/external LR-switch14.3.5.4 Operation principleThe function block Local remote (LOCREM) handles the signals coming from thelocal/remote switch. The connections are seen in Figure 333, where the inputs onfunction block LOCREM are connected to binary inputs if an external switch is used.When the local HMI is used, the inputs are not used. The switching between externaland local HMI source is done through the parameter ControlMode. The outputs fromthe LOCREM function block control the output PSTO (Permitted Source To Operate)on Bay control (QCBAY).Section 14 1MRK502052-UEN BControl714Technical manual