Table 658:SSCBR Output signalsName Type DescriptionOPENPOS BOOLEAN CB is in open positionCLOSEPOS BOOLEAN CB is in closed positionINVDPOS BOOLEAN CB is in Invalid PositionTRCMD BOOLEAN Open command issued to CBTRVTOPAL BOOLEAN CB open travel time exceeded set valueTRVTCLAL BOOLEAN CB close travel time exceeded set valueOPERALM BOOLEAN Number of CB operations exceeds alarm limitOPERLO BOOLEAN Number of CB operations exceeds lockout limitCBLIFEAL BOOLEAN Remaining life of CB reduced to Life alarm levelMONALM BOOLEAN CB 'not operated for long time' alarmIPOWALPH BOOLEAN Accum I^CurrExponent integr over CB open traveltime exceeds alarm limitIPOWLOPH BOOLEAN Accum I^CurrExponent integr over CB open traveltime exceeds lockout limitSPCHALM BOOLEAN Spring charging time has crossed the set valueGPRESALM BOOLEAN Pressure below alarm levelGPRESLO BOOLEAN Pressure below lockout level16.4.5 SettingsTable 659:SSCBR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnGlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base ValuegroupsPhSel Phase L1Phase L2Phase L3- - Phase L1 Phase selectionRatedOperCurr 100.00 - 5000.00 A 0.01 1000.00 Rated operating current of the breakerOperNoRated 1 - 99999 - 1 10000 Number of operations possible at ratedcurrentRatedFltCurr 500.00 - 99999.99 A 0.01 5000.00 Rated fault current of the breakerOperNoFault 1 - 10000 - 1 1000 Number of operations possible at ratedfault currenttTrOpenAlm 0.000 - 0.200 s 0.001 0.040 Alarm level for open travel timetTrCloseAlm 0.000 - 0.200 s 0.001 0.040 Alarm level for close travel timeOperAlmLevel 0 - 9999 - 1 200 Alarm level for number of operationsOperLOLevel 0 - 9999 - 1 300 Lockout level for number of operationsAccSelCal Aux ContactTrip Signal- - Trip Signal Accumulated energy calculation selectionTable continues on next pageSection 16 1MRK502052-UEN BMonitoring898Technical manual