4 PKE-SWD-32, interface for motor-starter combination with PKE PKE12/324.9 Programming114 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com4.9.1.8 Type of trip block (TYPE)The modular design of the PKE electronic motor-protective circuit-breakerenables several different current ranges to be covered. A different PKE tripblock is inserted into the PKE basic device depending on the current rangerequired. The following trip blocks of the type “Advanced” can be combinedwith the two PKE basic devices PKE12 and PKE32.Table 12: Combination options of the PKE basic device with PKE trip blockThe type of PKE trip block is mapped via the TYPE bit field (input byte 4,Bit 0 - 2). The values of this bit field are assigned to the following PKE tripblocks:Table 13: Bit field Type of trip block4.9.1.9 Time delay setting (CLASS)The CLASS bit field shows the value of the setting dial on the PKE trip blockfor the time lag class of the overload release. The setting points of the timelag class dial are assigned to the following values of the CLASS bit field.Table 14: Bit field Time delay setting (CLASS)→ If the communication module PKE-SWD-32 is commissioned(i.e. by removing and replugging the SWD device connector onthe PKE-SWD-32) while the thermal motor image of the PKEmotor-protective circuit-breaker has the value 100 % or higher,the contactor is not operational until the value is below the100 % mark of the thermal image.Base device PKE-XTUA-1,2 PKE-XTUA-4 PKE-XTUA-12 PKE-XTUA-32PKE12 ✓ ✓ ✓ XPKE32 X X ✓ ✓Field Value Control option part no.TYPE 0x0 PKE-XTUA-1,20x1 PKE-XTUA-40x2 PKE-XTUA-120x3 PKE-XTUA-320x4 Not defined0x5 Not defined0x6 Not defined0x7 Not defined→ The TYPE bit field can likewise be read as an acyclical dataobject (→ Section 4.9.4, "Acyclic data", page 121).