13 Appendix13.7 Technical dataSmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 26513.7.2 I/O modules, digitalEU5E-SWD-8DX EU5E-SWD-4DX EU5E-SWD-4D2R EU5E-SWD-4D4D/EU5E-...-4D4D-REU5E-X8DGeneralStandards IEC/EN 61131-2, EN 50178Dimensions W x H x D mm 35 x 90 x 101 35 x 90 x 101 35 x 90 x 101 35 x 90 x 101 35 x 90 x 101Weight kg 0.1 0.1 0.1 0.1 0.1Mounting DIN-rail IEC/EN 60715, 35 mmMounting position verticalAmbient mechanical conditionsDegree of protection (IEC/EN60529,EN50178, VBG 4)IP20 IP20 IP20 IP20 IP20Vibrations (IEC/EN 61131-2:2008)Constant ampli-tude 3.5 mmHz 5 - 8.4 5 - 8.4 5 - 8.4 5 - 8.4 5 - 8.4Constant accelera-tion, 1 gHz 8.4 - 150 8.4 - 150 8.4 - 150 8.4 - 150 8.4 - 150Mechanical shockresistance (IEC/EN60068-2-27)semi-sinusoidal 15 g/11 msImpactresis-tances9 9 9 9 9Drop to IEC/EN 60068-2-31Dropheight50mm 50 50 50 50Free fall, packaged(IEC/EN 60068-2-32)m 0.3 0.3 0.3 0.3 0.3Electromagnetic compatibility (EMC)Overvoltage category II II II II IIpollution degree 2 2 2 2 2Electrostatic discharge (IEC/EN 61131-2:2008)Air discharge(Level 3)kV 8 8 8 8 8Contact discharge(Level 2)kV 4 4 4 4 4Electromagnetic fields (IEC/EN 61131-2:2008)80 - 1000 MHz V/m 10 10 10 10 101.4 - 2 GHz V/m 3 3 3 3 32 - 2.7 GHz V/m 1 1 1 1 1Radio interference suppression(SmartWire-DT) EN55011Class A Class A Class A Class A Class ABurst (IEC/EN 61131-2:2008, Level 3)Supply cables 2 kV 2 kV 2 kV 2 kV 2 kVSignal cables 1 kV 1 kV 1 kV 1 kV 1 kVSmartWire-DT cables 1 kV 1 kV 1 kV 1 kV 1 kVSurge (IEC/EN 61131-2:2008, Level1)– Supply cables 0.5 kV – Supply cables 0.5 kV Supply cables 0.5 kV