10 SmartWire-DT universal module M22-SWD-NOP and M22-SWD-NOP-C10.5 CommissioningSmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 22310.4.2 Base mountingUniversal module M22-SWD-NOPC is fitted to circuit card M22-SWD-I...-LP… in surface mounting enclosure M22-I….To do so, proceed as follows:▶ Insert the printed circuit board into the surface mounting enclosure.Ensure that the PCB is pointing in the correct direction. The direction ofthe arrow defines the arrangement of the modules. (the gateway is to theleft of the IN code.)▶ Equip the slots with the M22-SWD-NOPC universal module. Ensure thatthe mounting position is correct (status LED must be at the top). Equipunused slots with the link M22-SWD-SEL8-10.Figure 84: Universal module M22-SWD-NOPC in enclosure M22-I310.5 CommissioningThe automatic addressing of all modules in the SmartWire-DT network is per-formed via the gateway during commissioning. Press the configuration but-ton on the gateway.During address assignment, the SmartWire-DT diagnostic LED at the back ofthe M22-SWD universal module will flash. Once the addressing process iscompleted, the LED indicates a green continuous light.10.5.1 Exchange of modules132132132INOUTOFFONON OFFM22-SWD4-SF8-20M22-SWD4-SM8-20M22-I…ATTENTIONSwitch off the entire SmartWire-DT system before replacingSmartWire-DT universal modules.ATTENTIONThe order of the SmartWire-DT units must not be altered.