10 SmartWire-DT universal module M22-SWD-NOP and M22-SWD-NOP-C10.3 EngineeringSmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 221Figure 81: M22-SWD-NOPC in enclosure M22-I310.3 EngineeringIn the PLC’s control configuration, program the SmartWire-DT modules thatwill be required at a later date in addition to the ones that will be installed andused immediately. For modules that are to be replaced with a universal mod-ule, parameter “Replacement by universal module” must be set to“allowed” in the Module Properties dialog In the control configuration. Youcan then fit a universal module in place of this SmartWire-DT module in thenetwork.In the user program scan whether the the configured SmartWire-DT moduleor a universal module is fitted. Bit 7 (SUBST) in the first input byte is set if auniversal module is fitted in place of the software-configured module. Theprogram flow must be controlled according to this information.M22-(C)K(C)...M22-(C)K(C)...M22-SWD-KC11M22-SWD-LEDC...M22-SWD-SEL-8-10M22-SWD-NOPC2 3 12 3 1132132132INOUTOFFONINOUTPUSH!PUSH!