2 I/O modules EU5E-SWD…2.13 Analog module EU5E-SWD-2A2ASmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 552.13.4 InstallationFigure 23: Connecting inputs and supply of module EU5E-SWD-2A2A▶ Connect the sensors to the corresponding inputs I0 to I1.▶ Connect the actuators to the corresponding outputs Q0 to Q1.▶ Connect the 24 V power supply for the card.2.13.5 ParameterizationWith the programming system’s control configurator, users can define thesensor/actuator model, measured value refresh rate and averaging.This setting applies to all analog inputs. The specified value is the refreshtime for the SmartWire-DT network. An averaging function that smoothsinput signal fluctuations can be activated separately.2.13.6 Fieldbus-specific characteristicsField bus CANopenU/I0 V24 V DC24 V0 V+U/I+++I0–I1–I1+I0+Q0–Q1–Q1+Q0+Parameter Setting options Basic SettingSensor type I0 Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)Sensor type I1 Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)Actuator model Q0 Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)Actuator model Q1 Voltage (0 - 10 V), current (0 - 20 mA) Voltage (0 - 10 V)Parameter Value (reading refresh rate) AveragingOn (default) OffReading refresh rate 20 ms 1100 ms (default setting) 5 measurement cycles200 ms 10 measurement cycles500 ms 25 measurement cycles