7 Pilot devices M22-SWD…7.2 M22-SWD front mountSmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 187Field bus EthercatPlease note the general information for configuring parameters→ Chapter 12 “Using SWD modules with the EtherCAT field bus”, page247, particularly→ Section “ Device options”, page 247.Device index: sub-index 22Parameter data length: 0x07.Structure of parameter byte 1:Table 51: Structure of parameter byte 04, 5 Scroll speed Bit 4 Bit 50 0 = Increase every detent0 1 = Increase every 2 detents1 0 Increase every 4 detents1 1 = Increase every 8 detents6 Reset with pushbutton 0 = Off1 = On7 Suppress 0x2E diagnostics 0 = "Pushbutton fault" (0x2E) will be signaled1 = "Pushbutton fault" (0x2E) will not be signaledBit Function Configuration0 Count direction 0 = The count will increase when the encoder is turnedclockwise1 = The count will increase when the encoder is turned counter-clockwise1 Quick scrolling 0 = Off1 = On2, 3 Reading refresh rate Bit 2 Bit 30 0 20 ms0 1 100 ms1 0 200 ms1 1 500 msBold values indicate the default settings.Bit Function ConfigurationBold values indicate the default settings.