7 Pilot devices M22-SWD…7.3 M22-SWD base fixingSmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 191One SmartWire-DT function element is used per slot. Correspondingly moreefficient function elements are used for the combined function of a luminouscommand device or for the realization of a multi-step switch.A luminous pushbutton, which previously had to be realized as a combinationof several elements, can now be realized simply by means of one combina-tion element (LED indicator + contact element = M22-SWD-K11LEDC).M22-SWD-KC11This function element replaces the previous contact elements M22-KC10/KC01. It provides a changeover contact by means of which both a breakerand maker function can be realized. The function element is used in combina-tion with M22 (pushbutton) actuators.M22-SWD-KC22This function element replaces multiple combinations of the previous contactelements M22-KC10/KC01. It provides two changeover contacts, by meansof which control switches can be operator controlled with up to three-posi-tion indication.M22-SWD-LEDC…This function element is used in combination with the indicator lights M22-L.... White, blue, green or red are available as colours.M22-SWD-K11LEDC… (multiple function elements)→ Non-used slots have to be equipped with the SmartWire-DTbridge M22-SWD-SEL8-10, otherwise the SmartWire-DT net-work will be interrupted.→ The PCBs contain a switchable terminating resistor for theSmartWire-DT network. If the surface mounting enclosure is thelast slave in the network, the terminating resistor must beswitched on.→ You can also obtain information about terminating resistors andon the use of the SWD link via the software program SWD-Assist.http://www.eaton.eu/software→ Further M22-KC10-/KC01 contact elements can be installedhere in the free locations in the surface mounting enclosure.A possible application is, for example, conventional switchingvia an M22-K... contact element and the reporting of this pro-cess to the PLC via the M22-SWD-K11 function element.→ Further M22-KC... contact elements can be installed here in thefree locations in the surface mounting enclosure.