2 I/O modules EU5E-SWD…2.5 InstallationSmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 232.5 InstallationThe SmartWire-DT input/output modules are envisaged for top hat mounting.They must be installed in a vertical position.▶ Mount the module on the top hat rail.Figure 6: Mounting on top-hat rail▶ Connect the 8-pole SmartWire-DT cable to the SmartWire-DT socket onthe device top.2.5.1 Connecting signal and supply cables▶ Connect the inputs/outputs and, if applicable, the supply cables to thepush-in terminals,▶ observing the permissible cable cross-sections.2.5.2 Terminal capacities• flexible: cross-section 0.25 mm² to 1.5 mm², with the ferrule (minimumlength 8 mm)• solid: 0.25 to 1.5 mm²• AWG24 to AWG162.5.3 Wiring of analog sensors/actuators▶ Only use shielded cables for connection.▶ Route the cables separately from power leads or signal cables that carrydifferential voltages.▶ Depending on the prevailing electromagnetic environment, one or bothends of the shielding should be earthed.▶ Connect the shielding with the module’s 0 V supply.→ Detailed instructions explaining how to assemble an SWD4-8SF2-5 SmartWire-DT external device plug onto an 8-pin Smart-Wire-DT ribbon cable can be found in the "SmartWire-DT, TheSystem" manual, in the "Mount the external device plug" sec-tion.12