2 I/O modules EU5E-SWD…2.8 Digital module EU5E-SWD-4D4D32 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com2.8 Digital module EU5E-SWD-4D4D2.8.1 INTRODUCTIONThe SmartWire-DT I/O module EU5E-SWD-4D4D provides four digital inputsI0 to I3 and four digital outputs Q0 to Q3.Diverse sensors can be integrated into the SmartWire-DT network via theinputs.The short-circuit proof outputs are used to drive actuators.The inputs'/outputs' status is indicated with the help of LEDs.The SmartWire-DT diagnostic LED is used to signal the network's/module'sstatus.2.8.2 Surface mountingFigure 12: Connections of the modules EU5E-SWD-4D4D2.8.3 EngineeringThe maximum current draw for each output is 0.5 A. The outputs are short-circuit proof. On short circuit the SmartWire-DT diagnostics LED flashes andthe diagnostic bit is set in the user program. When the short circuit isremoved, the supply voltage is automatically applied again.abcdfea SmartWire-DT cable with external device plugb SmartWire-DT diagnostics LEDc Status LEDs of the inputs and outputsd I0 – I3 (inputs)e Q0 – Q3 (outputs)f 0-V-24-V connection