2 I/O modules EU5E-SWD…2.9 Digital module EU5E-SWD-4D4D-RSmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 41This ensures that undesired changes will not occur at the outputs when thecontroller is started.Output configured as non-retentive (default setting):Driving will be based on simple output setting and resetting.2.9.7.3 DiagnosticsIn case of diagnosis, the module reports the following fault cause (bit 4 ininput byte 0 is set):7 6 5 4 3 2 1 0– – – – Q3 Q2 Q1 Q0Bit Designation MeaningOutput configured as retentiveMeaningOutput configured as non-retentiveBit 1 Bit 0 Bit 10 Q0R 0 0 No Change0 1 Output OFF1 Q0S 1 0 Output ON 1 Output ON1 1 No Change 0 Output OFFBit 3 Bit 2 Bit 32 Q1R 0 0 No Change0 1 Output OFF3 Q1S 1 0 Output ON 1 Output ON1 1 No Change 0 Output OFFBit 5 Bit 4 Bit 54 Q2R 0 0 No Change0 1 Output OFF5 Q2S 1 0 Output ON 1 Output ON1 1 No Change 0 Output OFFBit 7 Bit 6 Bit 76 Q3R 0 0 No Change0 1 Output OFF7 Q3S 1 0 Output ON 1 Output ON1 1 No Change 0 Output OFFValue Description0x13 Short-circuit/overload on at least one output