13 Appendix13.7 Technical data282 SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.comSurge (IEC/EN 61131-2:2008, Level 1) Figure 91: Performance criterion B(tested with 0.5kV/0.5kV)Radiated RFI(IEC/EN 61131-2:2008, Level 3)V 10Ambient climatic conditionsOperating ambient temperature (IEC 60068-2) °C -30 up to +60Condensation Must be prevented with suitable measuresStorage °C -30 up to +85Relative humidity, non-condensing (IEC/EN60068-2-30)% 5 – 95SmartWire-DT interfaceModule type SmartWire-DT module (slave)Baud rate setting AutomaticStatus SmartWire-DT LED GreenConnection Pin contact, 8 pole;Connector: blade terminal SWD4-8MF2Device supply voltageSWD moduleU SWD V DC,(%)14.5 (±3)Current consumption at U SWD → Page 253Potential isolationFrom supply voltage UAUXFrom 24 VDC external supply voltageFrom the light/acoustic modulesYesSupply voltage AUXRated operating voltage U e VDC,(%)24 (-15/+20)Residual ripple % –max. current consumption A 0.9 1.5Protection against polarity reversal YesPotential isolationFrom 24 VDC external auxiliary powerFrom device supply voltage for SmartWire-DTmodules USWDYesFrom the light/acoustic modules noExternal supply voltage 24 V DCConnection type Push-Insolid mm2 0.25 – 1.5flexible with ferrule1) mm2 0.25 – 1.5UL/CSA solid or stranded AWG 24 – 16Rated operating voltage U e VDC,(%)24 (-15/+20)Residual ripple % –max. current consumption A 0.9 1.5Protection against polarity reversal YesPotential isolationSL4-SWD SL7-SWD