No. Name Setting Range Defaulto2-04 Drive Model Selection - Depending on drivesizeNote: 1. Refer to Defaults by Drive Model and Duty Rating ND/HD on page 204 for a list of o2-04 settings and parameters that change dependingon the drive model selection.2. Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate properly.3. This parameter is not reset to the default value when the drive is initialized using A1-03.n o2-05: Frequency Reference Setting Method SelectionDetermines if the ENTER key must be used to input a frequency reference from the digital operator.No. Name Setting Range Defaulto2-05 Frequency Reference Setting Method Selection 0 or 1 0Setting 0: ENTER Key RequiredEvery change in the frequency reference setting on the digital operator has to be finalized by pressing the ENTER key beforeit becomes effective.Setting 1: ENTER Key Not RequiredThe output frequency changes immediately when the reference is changed by the UP and DOWN key on the digital operator.The ENTER key does not need to be pressed. The frequency reference is saved five seconds after the Up or DOWN key hasbeen released.If an undervoltage (Uv) error occurs within 5 seconds of pressing the ENTER key, the frequency reference will not be savedto memory.n o2-06: Operation Selection when LED Operator is DisconnectedDetermines if the drive will stop when an external LED operator (JVOP-182) is removed in LOCAL mode or with b1-02 setto 0.No. Name Setting Range Defaulto2-06 Digital Operator Disconnection Operation 0 or 1 0Setting 0: Continue OperationThe operation is continued.Setting 1: Trigger a FaultThe operation is stopped and an “oPr” fault is triggered. The motor coasts to stop.u o3: Copy FunctionUse o3 parameters to Read, Copy, and Verify the parameter settings to and from the drive using an LED operator (option).n o3-01 Copy Function SelectionParameter o3-01 selects the copy function operation.No. Name Setting Range Defaulto3-01 Copy Function Selection 0 to 3 00: No Action1: READAll parameters are copied from the drive to the LED operator.2: WRITEAll parameters are copied from the LED operator to the drive.3: VERIFYParameter settings in the drive are compared to those in the LED operator.Note: When using the copy function, the drive model number (o2-04) and the software number (U1-14) must match or an error will occur.5.9 o: Operator Related SettingsYASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual 1235 Parameter Detailshttp://nicontrols.com