C.5 MEMOBUS/Modbus Setup Parametersu MEMOBUS/Modbus Serial CommunicationThis section describes parameters necessary to set up MEMOBUS/Modbus communications.n H5-01: Drive Slave AddressSets the drive slave address used for MEMOBUS/Modbus communications.Note: After changing this parameter, the power must be cycled to enable the new setting.No. Name Setting Range DefaultH5-01 Drive Slave Address 0 to FF <1> 1F<1> If the address is set to 0, no response will be provided during communications.For serial communications to work, each individual slave drive must be assigned a unique slave address. Setting H5-01 to anyvalue besides 0 assigns the drive its address in the network. Slave address don't need to be assigned in sequential order, buteach address needs to be unique so that no two drives have the same address.n H5-02: Communication Speed SelectionSets the MEMOBUS/Modbus communications speed.Note: After changing this parameter, the power must be cycled to enable the new setting.No. Name Setting Range DefaultH5-02 Communication Speed Selection 0 to 5 3H5-02 Communication Speed0 1200 bps1 2400 bps2 4800 bps3 9600 bps4 19200 bps5 38400 bpsn H5-03: Communication Parity SelectionSets the parity used for MEMOBUS/Modbus communications.Note: After changing this parameter, the power must be cycled to enable the new setting.No. Name Setting Range DefaultH5-03 Communication Parity Selection 0 to 2 0Setting 0: No ParitySetting 1: Even ParitySetting 2: Odd Parityn H5-04: Stopping Method after Communication ErrorSelects the stopping method after a communications error (CE) has occurred.No. Name Setting Range DefaultH5-04 Stopping Method after Communication Error 0 to 3 3Setting 0: Ramp to Stop Using Current Accel/Decel TimeSetting 1: Coast to StopSetting 2: Fast-stop Using C1-09C.5 MEMOBUS/Modbus Setup Parameters214 YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manualhttp://nicontrols.com