n o3-02 Copy Function READ PermissionParameter o3-02 can be used to prevent accidentally overwriting the data stored in the operator.No. Name Setting Range Defaulto3-02 Copy Function READ Permission 0, 1 00: READ ProhibitedThe data in the operator are write protected. The READ operation cannot be performed.1: READ PermittedThe data in the operator are not write protected. The READ operation can be performed.u o4: Maintenance Monitor Settingsn o4-01: Accumulated Operation Time SettingParameter o4-01 sets the cumulative operation time and allows the user to set the starting value of the accumulated operationtime displayed in monitor U4-01.Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will alsobe displayed in monitor U4-01.No. Name Setting Range Defaulto4-01 Accumulated Operation Time Setting 0 to 9999 0n o4-02: Accumulated Operation Time SelectionSelects the conditions for what is to be considered “accumulated operation time.” Accumulated operation time is displayed inU4-01.No. Name Setting Range Defaulto4-02 Accumulated Operation Time Selection 0 or 1 0Setting 0: Power On TimeThe drive logs the time it is connected to a power supply, no matter if the motor is running or not.Setting 1: Run TimeThe drive logs the time that the output is active, i.e., whenever a Run command is active (even if the motor is not rotating) ora voltage is output.n o4-03: Cooling Fan Maintenance SettingSets the value of the cooling fan operation time base value used for the maintenance value displayed in U4-04. Be sure to resetthis parameter back to 0 if the cooling fan is replaced.Note: 1. The value in o4-03 is set in 10 h units.2. The actual maintenance time depends on the environment the drive is used in.No. Name Setting Range Defaulto4-03 Cooling Fan Operation Time 0 to 9999 0n o4-05: Capacitor Maintenance SettingSets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expectedperformance life. This value should be reset to 0 when the DC bus capacitors have been replaced.Note: The actual maintenance time will depend on the environment the drive is used in.No. Name Setting Range Defaulto4-05 Capacitor Maintenance Setting 0 to 150% 0%n o4-07: DC Bus Pre-charge Relay Maintenance SettingSets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expectedperformance life. This value should be reset to 0 when the relay has been replaced.Note: The maintenance actual time depends on the environment the drive is used in.5.9 o: Operator Related Settings124 YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manualhttp://nicontrols.com