4.8 Verifying and Backing Up Parameter SettingsCheck changes to parameter settings using the Verify function. Refer to Verifying Parameter Changes: Verify Menu onpage 66.Save the verified parameter settings. Change the access level or set a password to the drive to prevent accidental modificationof parameter settings.u Parameter Access Level: A1-01Setting the Access Level for “Operation only” (A1-01 = 0) allows the user to access parameters A1-oo and Uo-oo only.Other parameters are not displayed.No. Parameter Name Description SettingRange DefaultA1-01 Access LevelSelectionSelects which parameters are accessible via the digital operator.0: Operation only (A1-01 and A1-04 can be set and monitored. U parameters can bemonitored)2: Advanced Access Level (All parameters can be set and monitored)0, 2 2u Password Settings: A1-04, A1-05The user can set a password to the drive to restrict access. The password is selected via parameter A1-05. The selected passwordmust be entered in parameter A1-04 to unlock parameter access (i.e., parameter setting A1-04 must match the valueprogrammed into A1-05). The following parameters cannot be viewed or edited until the value programmed into A1-04correctly matches the value as programmed in parameter A1-05: A1-01 and A1-03.Note: Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and simultaneously depress the key and thekey.u Copy Function (Optional)Parameter settings can be copied to another drive to simplify parameter restoration or multiple drive setup. The RS-232CInterface Unit (Removable Type) (SI-232/JC) is required to use the following options with J1000 drives:n USB/Copy Unit (JVOP-181)The copy unit is an external option connected to the drive to copy parameter settings to another drive. It includes a USB adapterto connect the drive to a PC.n LED Operator (JVOP-182)The LED operator operates the drive and supports copying, importing, and verifying parameter settings.Note: Use of the LED operator requires that the drive is running drive software version PRG: 1010 or later.n Drive Wizard PlusDrive Wizard Plus is a PC software tool for parameter management, monitoring, and diagnosis. Drive Wizard Plus can load,store, and copy drive parameter settings. For details, refer to Help in the Drive Wizard Plus software.The installation files can be obtained at no charge from:U.S.: http://www.yaskawa.com4.8 Verifying and Backing Up Parameter Settings72 YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manualhttp://nicontrols.com