No. Parameter Name Setting Range Defaultb1-08 Run Command Selection while in Programming Mode 0 to 2 0Setting 0: DisabledA Run command is not accepted while the digital operator is in Programming Mode.Setting 1: EnabledA Run command is accepted in any digital operator mode.Setting 2: Prohibit Programming During RunIt is not possible to enter the Programming Mode as long as the drive output is active.n b1-14: Phase Order SelectionSets the phase order for drive output terminals U/T1, V/T2, and W/T3.No. Parameter Name Setting Range Defaultb1-14 Phase Order Selection 0 or 1 0Setting 0: Standard Phase OrderSetting 1: Switched Phase Ordern b1-17: Run Command at Power UpThis parameter is used to determine whether an external Run command that is active during power up of the drive will startthe drive or not.No. Parameter Name Setting Range Defaultb1-17 Run Command at Power Up 0 or 1 0Setting 0: Run Command at Power Up is not IssuedThe Run command has to be cycled to start the drive.Note: For safety reasons, the drive is initially set up not to accept a Run command at power up (b1-17 = "0"). If a Run command is issued at powerup, the RUN indicator LED will flash quickly. Change parameter b1-17 to 1 if a Run command active at power up shall be accepted by thedrive.Setting 1: Run Command and Power Up is IssuedAn external Run command active during power up is issued and the drive starts to operate the motor as soon as it gets readyfor operation (i.e. once the internal start up process is complete).WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will beginrotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior topowering up the drive. Failure to comply may cause serious injury.u b2: DC Injection BrakingThese parameters determine how the DC Injection Braking feature operates. Parameters involving the starting frequency,current level, braking time are located here.n b2-02: DC Injection Braking CurrentSets the DC Injection Braking current as a percentage of the drive rated current. If set to larger than 50%, the carrier frequencyis automatically reduced to 1 kHz.No. Name Setting Range Defaultb2-02 DC Injection Braking Current 0 to 75% 50%The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft.Increasing the current level will increase the amount of heat generated by the motor windings. This parameter should only beincreased to the level necessary to hold the motor shaft.n b2-03: DC Injection Braking Time at StartSets the time of DC Injection Braking at start. It can be used to stop a coasting motor before restarting it or to apply a brakingtorque at start. Disabled when set to 0.00 s.5.2 b: ApplicationYASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual 835 Parameter Detailshttp://nicontrols.com