Register No. Contents00D0HCPF Contents 1bit 0, 1 Reservedbit 2 A/D Conversion Error (CPF02)bit 3 to 5 Reservedbit 6 EEPROM data fault (CPF06)bit 7 Reservedbit 8 EEPROM Serial Communications Fault (CPF08)bit 9 to A Reservedbit B RAM Fault (CPF11)bit C FLASH Memory Fault (CPF12)bit D Reservedbit E Control Circuit Fault (CPF14)bit F Reserved00D1HCPF Contents 2bit 0 Reservedbit 1 Timing Fault (CPF17)bit 2 Control Circuit Fault (CPF18)bit 3 to 5 Reservedbit 6 A/D Conversion Fault (CPF22)bit 7 PWM Feedback Fault (CPF23)bit 8 Drive capacity signal fault (CPF24)bit 9 to F Reserved00D2H to 00FBH Reserved<1> Units are determined by parameter H5-13.<2> The communication error log is stored until the fault is reset.u Broadcast MessagesData can be written from the master to all slave devices at the same time.The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will notrespond.Register No. Contents0001HDigital Input Commandbit 0 Forward Run (0: Stop 1: Run)bit 1 Direction Command (0: Forward, 1: Reverse)bit 2, 3 Reservedbit 4 External Faultbit 5 Fault Resetbit 6 to B Reservedbit C Multi-Function Digital Input S5 (enabled when bit C of register 000FH is ON)bit D to F Reserved0002H Frequency Reference 30000/100%C.10 MEMOBUS/Modbus Data Table228 YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manualhttp://nicontrols.com