7 In-Tank Setup Programmable Minimum Water Threshold7-16Programmable Minimum Water ThresholdIf necessary, press STEP until you see the message:Note: This message does not appear when Float Type has been set to Custom.When there is not water in the tank, but the water height measurement is not 0.0, the water float is resting on alayer of debris on the bottom of the tank. The Water Minimum Threshold sets the level.To enter the Water Minimum Threshold, press CHANGE and enter the required threshold within the range of 0.0to 1.0 inches. For example, you enter 0.800.. Press ENTER to confirm the entry. The display will confirm your entrywith the message:Max or Label VolIf necessary, press STEP until you see the message:Maximum or Label Volume (in international installations this is considered safe working capacity) alarm warns whenthe level of fluid in the tank exceeds the volume you enter here. Set this value at a level higher than the High LevelLimit [see Figure 7-1].Press CHANGE and enter the value. Press ENTER to confirm your entry. The system displays:Overfill LimitIf necessary, press STEP until you see the message:Overfill Limit warns of a potential overfill only during a bulk delivery. When the volume reaches this limit, the systemcan activate an on-site overfill alarm and trigger a printout showing the tank #, date, time, and product. Set thispercentage no greater than 90% of the tank’s capacity (in international installations set this percentage no greaterthan 99% of label volume) see Figure 7-1.Press CHANGE. Enter the percent limit and press ENTER to confirm your entry:T1: (Product Label)WATER MINIMUM: 0.000WATER MINIMUM: 0.800PRESS TO CONTINUET1: (Product Label)MAX OR LABEL VOL: 000000MAX OR LABEL VOL: XXXXXXPRESS TO CONTINUET1: (Product Label)OVERFILL LIMIT: 000%OVERFILL LIMIT: XX%PRESS TO CONTINUE