26-326 Smart Sensor Setup Mag Sensor Setup• Vapor Pressure• Mag Sensor• Vac Sensor• ATMP Sensor (NOTE: The atmospheric pressure [ATMP] sensor is resident in the Smart Sensor / PressModule. One ATMP sensor is required with Vac Sensor systems per site. You only need to configure the ATMPsensor, there is no setup [other than assigning a label]. A Setup Data Warning will be posted for all Vac Sensorsif an ATMP sensor is not present and configured)• UnknownMag Sensor SetupIf the Mag Sump Sensor you installed has NO programmable features (i.e., alarm upgrade delay, water warningheight, or water alarm height), you will not be able to enter Mag Sensor Setup after entering Smart Sensor labeland Sensor Category.If necessary, press STEP until you see the message:Press ENTER:This display appears if the alarm upgrade delay has been factory set to programmable. This is the time in hoursthat all uncleared warnings will delay before upgrading to alarms. Also, this upgrade only applies to Smart Sensorwarnings that have been factory set to upgrade.If necessary, press CHANGE and enter the number of hours (up to 9999) to delay upgrades. Entering 0 disablesthe Alarm Upgrade Delay feature. Press ENTER to confirm your entry.Press STEP to continue.:This display appears only if the Water Warning has been factory set to programmable. This is the height in inches(or mm if metric units selected) at which the Water Warning will activate. Refer to your Smart Sensor setupprintout’s Min/Max Thresholds for the permissible range within which to select this value.If necessary, press CHANGE and enter the Water Warning height. Press ENTER to confirm your entry.Press STEP to continue.:This display appears only if the Water Alarm has been factory set to programmable. This is the height in inches (ormm if metric units selected) at which the Water Alarm will activate. Refer to your Smart Sensor Setup printout’sMin/Max Thresholds for the permissible range within which to select this value.If necessary, press CHANGE and enter the Water Alarm height. Press ENTER to confirm your entry.s 1: MAG SENSOR SETUPPRESS s 1: (Name)ALM UPGRADE DELAY: XXXXs 1: WATER WARNINGWATER HT > 0002.0s 1: WATER ALARMWATER HT > 0005.0