17 Reconciliation Setup Remote Report Format17-4Press STEP. The system displays the message:Press CHANGE. Enter the number of gallons (litres) of allowable variance. Press ENTER. The system confirmsyour entry with the message:Press STEP to continue.Remote Report FormatIf necessary, press STEP until you see the message:NOTE: This feature appears only when a remote printer is installed.You can choose between ROW and COLUMN printer formats. To maintain the default or current setting, pressSTEP. (The system displays the MODIFY TANK/METER MAP message.)To change the default or current setting, e.g., from ROW to COLUMN, press CHANGE, then press ENTER. Thesystem confirms your entry with the message:Press STEP to continue.Temp CompensationIf necessary, press STEP until you see the message:This feature allows you to choose whether or not to calculate Business Inventory Reconciliation (BIR) volumesusing the Programmable Temperature Compensation (TC) value. For information on entering this value, (See“Temperature Compensation Value” on page 13.). Select STANDARD (the default) if the meters are nottemperature compensated. Select TC VOLUME if the meters are temperature compensated (the calculation of allBIR volumes will be based on the TC value).Press STEP to accept STANDARD. Press CHANGE, then ENTER to select TC VOLUME. The system confirmsyour choice with the message:PERIODIC RECONCILIATIONALARM OFFSET: 000130ALARM OFFSET: XXXXXXPRESS TO CONTINUEREMOTE REPORT FORMATSELECT: ROWSELECT: COLUMNPRESS TO CONTINUETEMP COMPENSATIONSTANDARDTC VOLUMEPRESS TO CONTINUE