20 Groundwater Sensor Setup Groundwater Sensor Location20-2Press STEP. If more than one module is installed, the system automatically advances to the SENSOR CONFIGmessage for the next module. Up to 8 modules may be installed. Repeat the steps described above for eachmodule until you have entered configuration information (sensor positions) for all modules and the system displaysthe ENTER SENSOR LOCATION message.Groundwater Sensor LocationIf necessary, press STEP until you see the message:To enter the sensor location, press TANK/SENSOR repeatedly until the sensor you want appears on the secondline of the message (G1, G2, G3, etc.). Press CHANGE and enter the location (up to 20 alphanumericcharacters) of the selected sensor. Typical entries are: WELL #1, NEW CORNER, etc. (This information appearson sensor status and sensor alarm reports to make it easier to identify the location of the alarm.) Press ENTER toconfirm your entry:Press STEP to continue.Groundwater Sensor CategoryIf necessary, press STEP until you see the message:If necessary, press CHANGE until you see the correct category. The category options are:• ANNULAR SPACE • DISPENSER PAN• MONITOR WELL • STP SUMP• PIPING SUMPWhen the correct category displays, press ENTER.Setting Up Additional Groundwater SensorsIf you have additional sensors to configure, press STEP, if necessary, until you see the ENTER SENSORLOCATION message. Press TANK/SENSOR to select another sensor and follow the procedures describedabove, beginning with “Groundwater Sensor Location” on page 20-2.If you have entered setup information for all sensors, press FUNCTION to exit.ENTER SENSOR LOCATIONG1:G1: (Sensor Location)PRESS TO CONTINUEG1: (Sensor Location)CATEGORY:OTHER SENSORS