23 External Input Setup Pump Sense Setup Data23-4Pump Sense Setup DataIf necessary, press STEP until you see the message:NOTE: This message appears only if you chose Pump Sense for the External Input Type.You must identify the tank to which this Pump Sense input is assigned.To enter the tank number, press CHANGE until the desired Tank number is displayed. Press ENTER to confirmyour entry:SELECTING A DISPENSE MODEIf necessary, press STEP until you see the message:In this step you select the dispense mode of the tank. The choices are:• STANDARD - Only one pump feeds the line.• MANIFOLDED: ALTERNATE 1,2 - When a dispense starts, the pump in the tank with the greatest inventoryvolume will run until the dispense ends. See Auto Active Switchover below for optional selections with thisdispense mode.• MANIFOLDED: SEQUENTIAL1,2 - The tanks are pumped low one at a time. When the tank’s volume dropsbelow the entered Pump Threshold percentage, pumping will switch over immediately to the next available tankin the line manifolded set. Pumping will continue from the current tank for another 10 seconds to avoid adisruption in dispensing during the switch over. (see “Pump Threshold” on page 7-26).• MANIFOLDED: ALL PUMPS - All pumps on the line are run.• MANIFOLDED: ALTERNATE-HT 1,2 - When a dispense starts, the pump in the tank with the greatest fuel heightwill run until the dispense ends. See Auto Active Switchover below for optional selections with this dispensemode.To select Standard (the system default) press STEP. The system confirms your choice with the message:Press CHANGE to select another selection, then Press ENTER to confirm your choice.1. To prevent backfilling, the level of all tanks connected to the line will be monitored. If the level of any tank exceeds95% of the Max or Label Volume limit (see “Max or Label Vol” on page 7-16), the pump for that tank will also beturned on during dispensing. The state of the pump that was already ON will not be changed.2. At locations with manifolded fuel lines that have a mechanical line leak detector installed for each pump, the TLSConsole must be programmed for either Manifolded: Alternate, Manifolded: Alternate-HT or Manifolded:Sequential. Doing so ensures that each line meets the 3 GPH requirement.I1: SELECT TANKNONETANK #: (Product Label)PRESS TO CONTINUEQ1: ENTER DISPENSE MODEXXXXXXXXXS1: (Dispense Mode)PRESS TO CONTINUE