12-112 Volumetric Line Leak DetectionThis function allows you to enter information about Volumetric Line Leak Detectors (VLLDs) installed on productpipelines in the system. You must enter data individually for each line leak detector.VLLD SetupTo select Volumetric Line Leak Detector Setup, press FUNCTION until you see the message:Press STEP to continue.Activating VLLDsIf necessary, press STEP until you see the following message:This display allows you to activate the Line Leak Detectors in a module. In the active state, the detector attempts toconduct line leak tests whenever the dispensers are off. To activate a detector, you must replace the X with a 1. Toleave a detector inactive, choose an X for the position.To set up the detector, press CHANGE in response to the LINE CONFIG message until the correct choiceappears (1 to activate, X to deactivate). Press ENTER to confirm your choices. The system displays:NOTE: Slot 1 is the slot at the bottom (not the top) of the compartment as shown on the circuit directory inside theconsole door.Press STEP to continue. The system automatically displays a LINE CONFIG message for each Line Leak DetectorModule installed in the system. When you have configured all the modules, press STEP to display the ENTERPIPE LABEL message.Pipe Label and Tank IdentificationIf necessary, press STEP until you see the following message:This display allows you to enter a label that will identify the pipe being monitored (location, fuel type, etc.).If needed, press TANK/SENSOR to access any other Line Leak Detector in the system.LINE LEAK DETECTOR SETUPPRESS TO CONTINUELINE CONFIG - MODULE 1SLOT# - XSLOT# - 1PRESS TO CONTINUEENTER PIPE LABELP#: