11 Wireless Pressurized Line Leak Detection Tank Selection11-6ENTERING THE PRESSURE OFFSET VALUE FOR EACH TRANSDUCERPress MODE to return to the SETUP MODE, then FUNCTION until you see the message:Press STEP until you see the message:Press CHANGE and enter the Pressure Offset value for transducer W1. If necessary, press the left arrow key tochange the sign (+ or -). Note: enter the Offset value exactly as displayed in the Offset test result message(including + or - sign). Press TANK/SENSOR, to display another transducer. Press CHANGE to enter its PressureOffset value, then ENTER to confirm the change. Repeat this procedure until you have entered Offsets for alltransducers.Tank SelectionThis entry allows a tank’s WPLLD to act as a pump sense input for automatic in-tank leak detection, CSLD,catastrophic leak testing and other features. This step can only be used for tanks that are not already connected toa line leak detector. This message appears only if tanks have been configured in the In-Tank Setup procedure.For no selection press STEP to continue. If yes, press CHANGE until the tank number to which the particularWPLLD is connected appears, then press ENTER. The system confirms your choice with the message:Press STEP to continue.Selecting a Dispense ModeNOTE: This option will only appear if a tank has been selected for the WPLLD.If necessary, press STEP until you see the message:This entry asks you to select the dispense mode. You can select between:• STANDARD - Only one pump feeds the line.WPLLD LINE LEAK SETUPPRESS TO CONTINUEW 1: WPLLD NUMBER 1PRESSURE OFFSET: +XX.XW1: SELECT TANKNONET#: (Product Label)PRESS TO CONTINUEW1: ENTER DISPENSE MODEXXXXXXXXX