5-195 System Setup Custom Alarm LabelsPress ENTER to continue:If you have not entered a passcode, press CHANGE and enter a 6-digit numeric passcode, then press ENTER toaccept your entry:Press STEP to continue.If necessary, press CHANGE and enter the TLS Console serial number from the label on the bottom of theconsole. Press ENTER to accept your entry. Press STEP to continue:If necessary, press CHANGE and enter the Weights and Measures office number. Press ENTER to accept yourentry. Press STEP to continue.Custom Alarm LabelsIf necessary, press STEP until you see the message:This step allows you to enter up to 16 custom labels and indications per alarm (one per device with a maximum of16 devices), for up to 10 alarms, for a maximum of 160 labels, each up to 19 characters in length, and each withits own indication set. Only alarms that applicable to your site’s equipment configuration and features can becustomized.Your custom labels replace the system generated display/print alarm labels that are used in display messages,printouts, and RS-232 reports only. Alarm labels used in Autodial, Output Relay, WPLLD, PLLD, and VLLD linedisable setups, shown in the Autodial Alarm Label column of Table 5-1, will not change.After you have made a custom label change, you also select a custom indicator set for that alarm which determineswhat console indicator(s) are activated when the alarm is posted:• LCD: Display in the front panel screen - yes / no• Print: yes / no• Beep: Turn on the console beeper - yes / noTANK CHART SECURITYENTER PASSCODE->______<TANK CHART SECURITYCODE : 000000 This display appears if a passcode has not been entered (default). All zerosThis display appears if Tank Chart Security is enabled - a passcode other than all zerosdisables Tank Chart Security.has been entered. Enter the 6-digit numeric passcode and press ENTER.CODE: ******PRESS TO CONTINUECONSOLE SERIAL NUMBER:S/N : (serial number)WEIGHTS AND MEASURES:W&M: (weights and measures)CUSTOM ALARM LABELSPRESS