5 System Setup Line Annual Test Needed Warnings5-12The system monitors the amount of time since the last passed 0.1 gph (0.38 lph) line test. By enabling Line AnnualTest Needed Warnings, you can have the system provide a warning when a 0.1 gph line test has not been passed,or conducted in a specified number of days (0 to 365), and activate an alarm if a test has not been passed after awarning, or a specified number of days.To keep Line Annual Test Needed Warnings disabled, press STEP. (The system displays the Remote Printer PageEject or Print TC Volumes message.)ENABLE LINE ANNUAL TEST NEEDED WARNINGS AND ALARMSTo enable line annual warnings, press CHANGE. The system now displays:Press ENTER. The system confirms your choice with the message:Press STEP. The system now displays:Press CHANGE and enter the number of days after which you want the system to warn that a 0.1 gph (0.38 lph)line test has not been passed (0 to 365). Press ENTER. The system displays the message:Press STEP. The system displays the message:The default value is 355 days. If you do not want to accept the default, press CHANGE. Enter the number of daysafter which you want the system to alarm if a test has not been passed (0 to 365). This number should be higherthan the number you set for periodic warning. Press ENTER. The system displays the message:Press STEP. (The system displays the Remote Printer Page Eject or Print TC Volumes message.)DISABLE LINE ANNUAL TEST NEEDED WARNINGS AND ALARMSTo disable Line Annual Test Needed Warnings that are already enabled, press CHANGE in response to the LineAnnual Test Needed Warnings Enabled message and press ENTER. The system confirms your choice with themessage:Press STEP continue. (The system displays the Remote Printer Page Eject or Print TC Volumes message.)LINE ANN TST NEEDED WRNENABLEDENABLEDPRESS TO CONTINUELINE ANN TST NEEDED WRNDAYS = XXXDAYS = XXXPRESS TO CONTINUELINE ANN TST NEEDED ALMDAYS = XXXDAYS = XXXPRESS TO CONTINUEDISABLEDPRESS TO CONTINUE