24-124 Output Relay SetupOutput Relays allow you to assign alarm limits, line leak alarms, sensor alarms, and inputs from external devices tospecific relays. Signals from an alarm limit or device triggers the Output Relay assigned to it. You must enter dataindividually for each Output Relay. The data you enter tells the system the number, location, and name of OutputRelays installed.NOTE: If output relay modules are not installed, this function is not available.Selecting the Output Relay Setup FunctionTo select Output Relay Setup, press FUNCTION until you see the message:Press STEP to continue.Relay ConfigurationIf necessary, press STEP until you see the message:Use this display to tell the system which relay positions on a module are connected to external devices.HOW THE SYSTEM CONFIGURES OUTPUT RELAYSIf output relay modules are installed, the system recognizes the presence and module slot locations of each one.The system also establishes a module number based on the slot location. For example, if modules are installed inslots #9 and #13, the module in slot #9 automatically becomes module #1 and the module in slot #13 becomesmodule #2.As you tell the system which relay positions on a module are connected to external devices, the system establishesa number for each relay. For example, if there are relays in positions 2 and 4 of module 1, the relay in position 2becomes R2 and the relay in position 4 become R4.To indicate that one of the relay positions on the module is connected to an external device, choose the numbercorresponding to that position. There can be up to four relay positions for 4-Relay Modules and up to two positionsfor I/O Combo Modules. For example, if the position is two, choose “2” for the position. To indicate that a positionis not connected to an external device, choose X for that position.SPECIFYING OUTPUT RELAY POSITIONSTo specify whether position 1 is connected, press CHANGE until the correct choice appears (1 if the position isconnected, X if it is not). Press the Right Arrow key to move to position 2 and press CHANGE again until thecorrect choice appears. Repeat these steps until you have correctly specified all positions. When you have entereda choice for all positions, press ENTER to confirm your entry:OUTPUT RELAY SETUPPRESS TO CONTINUERELAY CONFIG - MODULE 1SLOT #: X X X XSLOT #: X X X XPRESS TO CONTINUE