7 In-Tank Setup Tank Density7-4To enter the Thermal Coefficient, press CHANGE and enter the coefficient in U.S. or Metric units, depending onthe units specified in System Setup (Be careful to add the correct number of zeros to the right of thedecimal point. An incorrect entry can cause test failures and other problems).Contact your authorized Veeder-Root Service Representative for thermal coefficients for British Imperial units.Press ENTER to confirm your entry. The system displays:Press STEP to continue.Tank DensityIf necessary, press STEP until you see the message:A value of 0 indicates that the density for the product in this tank has not been entered, or a delivery has ocurred,or the thermal coefficient changed. For Tank Density enter any one of the product’s values below (units are notentered):• Mass per unit volume at reference temperature (density),• Specific Gravity,• API number• A fourth way to enter Density is by entering the known Thermal Coefficient of the product in the tank (in thesetup step above) and letting the console automatically calculate Tank Density using the Thermal Coefficientvalue (density value is not displayed).If necessary, press CHANGE and enter the density of the product in this tank as shown in the example below:Press ENTER:If this value is accepted, it will be converted to actual density (but the user entered value is displayed).Used Water 0.00012 0.00022Washer Fluid 0.00047 0.00085Used Oil 0.00044 0.00079Table 7-1. Typical Thermal CoefficientsProductThermalCoefficient(U.S. Units)ThermalCoefficient(Metric Units)THERMAL COEFF: 0.000XXPRESS TO CONTINUET1: (Product Label)DENSITY :0.0000If Mass/Density is disabledthis window will not appear!T1: (Product Label)DENSITY :5.9987DENSITYPRESS TO CONTINUE:5.9987